Standard model for underground circulation conditions Modular Water Cooled Scroll Chiller
Specifications
SD standard model for underground circulation conditions
| Basic modules | EKWD021CRSD | EKWD032CRSD | EKWD043CRSD | |||
| Underground circulation mode | Nominal Cooling Capacity | kW | 76 | 113 | 153 | |
| Nominal Heating Capacity | kW | 79 | 115 | 159 | ||
| Total Power of Nominal Cooling Capacity | kW | 13 | 20.4 | 27.2 | ||
| Total Power of Nominal Heating Capacity | kW | 16.8 | 26.0 | 34.3 | ||
| Water flow | Application side | m³/h | 13.1 | 19.4 | 26.3 | |
| Heat source side | m³/h | 15.3 | 22.9 | 31.0 | ||
| Water pressure drop | Application side (air conditioner side) | kPa | 19 | 35 | 32 | |
| Heat source side | kPa | 26 | 20 | 19 | ||
| Heat exchanger type | Application side (evaporator) | Plate | Shell-and-tube | |||
| Heat source side (condenser) | Shell-and-tube | |||||
| Recommended total pipe diameter | Evaporator | mm | DN65 | DN65 | DN80 | |
| Condenser | mm | DN65 | DN65 | DN80 | ||
| Volume Adjustment | Steps | 2 | 3 | 4 | ||
| Regulation mode | Fuzzy control | |||||
| Compressor | Model | Fully hermetic volute | ||||
| Lubricant | Mineral oil (SUNISO 3GS) | |||||
| Modular Geothermal Ground Source Heat Pumps For Underground Circulation Conditions |
Company QR code Anytime Anywhere Mobile |
|||||